ProSeries CCD Early Warning Fire Detection Systems
If you are looking for a better alternative to laser based early
warning fire detection, you'll find it in the SAFE ProSeries line
of "Cloud Chamber Detection" (CCD) technology Incipient
Fire Detection (IFD) products. The wall mounting ProSeries early
warning fire detectors (and portable ProLocator "Fire Sniffer")
detect pre-smoke particles of combustion that are produced at the
earliest incipient stage of a fire, and they are complete unaffected
by dust and other airborne particulate.
IFD Cirrus ProSeries CCD Hybrid Air Sampling
IFD Detectors
|
|
CCD Technology provides the earliest early warning
fire detection |
|
|
Immune to dust, dirt, heat, cold, humidity and other
factors that typically cause False Alarms in other
detectors |
|
|
Large area coverage - up to 43,200 sq. ft with one
panel |
|
|
0.0000% to 100% obs/ft, and more sensitivity
combinations than any other air sampling
detector |
|
|
Drop in replacements for any air sampling detector
WITHOUT sampling pipe modification |
|
|
Less maintenance, and does not require costly
periodic re-calibration *More new features and
easier to operate |
|
|
Less costly than other
systems |

|
Pro X4 Series
CCD Technology IFD Products
|
|
IFD Cirrus ProSeries Specifications
|
Supply Voltage: 20 - 29 VDC |
|
Dimensions (WxHxD): |
|
PRO 100 Mini - 11.25" x 8.5 x 4.25" |
|
PRO 200 - 14.25" x10 x 4.5" |
|
PRO 200D - 14.25" x10 x 4.5" |
|
PRO 200DSC - 17" x 15 x 5.7" |
|
PRO X4 - 17.3" x 15.2" x 5.7 |
|
Pipe length: |
|
PRO 100 Mini - Up to 325 ft. |
|
PRO 200 - 4 pipes up to 650 ft. |
|
PRO 200D - 4 pipes up to 650 ft. |
|
PRO 200DSC - 4 pipes up 650 ft. |
|
PRO X4 - Max. over 1400 ft. |
|
Sample Holes: |
|
PRO 100 Mini - Up to 50 holes per zone with 30"x30"
spacing.* |
|
PRO 200, PRO 200D & PRO200DSC - Up to 100 holes
per zone, with 30'x30" spacing.* |
|
Pro X4 - Up to 12 Sample Heads per Zone with 30' x
30' spacing, up to 4 Zones |
|
Alarm Levels: 4 Adjustable |
|
Variable Sensitivity Settings: Each zone has
10 possible sensitivity settings per alarm level. Each
level can be changed 3 times per day and different f or
each day of the week. Other Indications: Supply Healthy,
Fault |
|
Sensitivity Range: 0.0000 to 100%
obs./ft. |
|
Event Log: 200 events stored on FIFO
basis |
|
ProSeries Options: CirrusPro Network, BMS
Interface, Alarm Panel Protocol |
|
|
ProLocator "Fire Sniffer" Portable
CCD Hybrid Air Sampling Detector
Early warning fire
detection is important, but how do you find the source of the
alarm? The ProLocator Fire Sniffer is the world's ONLY
portable CCD early warning fire detector that allows you to
"sniff" out the source of the fire or pre-fire event. The
ProLocator Fire Sniffer uses "Cloud Chamber Detection" (CCD)
Technology that detects particles of combustion. Similar in
operation to a Gieger Counter, the ProLocator Fire Sniffer
directs you to the source of the fire with audible and visual
indicators. Identifying the source of your early warning fire
alarm has never been easier.
|
Sensitivity Range: 0.0000 to 100%
obs./ft. |
|
Power: Battery operated with charger |
|
Dimensions (WxHxD): 12" x 11" x
4.25" |
|
Weight: 12 lbs. |
|
Unit Operating Temperature: 32° - 130°F (0 -
54°C) |
|
Location Indicator: LED and audible |
|
Other Indicators: Supply Health and
Fault |
|
|
|
AquaAlert Water Detection
Systems
AquaAlert Water Detection Systems make easy work of letting
you know promptly when a water leak has occurred. AquaAlert
is available in both "Spot" and "linear"
water leak detection and we can supply the system with a custom
graphic annunciator that will identify the location of the water
detection.
|
Area of Detection: Wire = Max. 5000 ft sq. Per zone
(Based on 15' centers) |
|
Spot Detector (For use in areas water will collect
E.G. Sumps/Drains) |
|
Number of Zones: Up to 4 (Single Zone , Four Zone or
Single Zone Distance Locating) |
|
Maximum Wire Lengths: 1000' ( We recommend 500' to
keep zones size manageable) |
|
Wire Spacing: 5', 10' or 15' On Center |
|
Power Input: 115VAC, 60Hz, .5 amps |
|
Battery Back Up: 12 VDC 1.2 amp/hr. Battery With
automatic charger
|
|
Indicators: LED type: for Alarm, Trouble and Power-on
Status |
|
Distance Locating Type: Digital Display (Footage
measurement) |
|
Size: 10" x 10" x 4" (254mm x 254mm x 102mm |
|
Contact Ratings: 1 Zone Unit - 1 Relay (Alarm and
Fault Combined) 2 - 8 Zone Unit - 2 Relays - Alarm
and Fault |
Spot Detector can be connected to any type
of warning device to alert you of water-based leakage.
The Spot Detector can also identify the location of the
problem to help you quickly make
repairs. |

|
|
ThermoCable
Linear Heat Detection Wire
SAFE Fire Detection, Inc. ThermoCable Linear Heat Detection
Wire offers longer operating distances and greater ease of
installation over competitive linear heat detection products.
It can be used with any certified fire alarm panel and ThermoCable
offers you savings on both the cost of the wire and the cost
of installation. ThermoCable is available in a variety of
alarm temperatures and it carries full FM, UL and ULC certifications,
among others. It's simple; a better linear heat detection
wire at a better price.
ThermoCable
Linear Heat Detection Wire
ThermoCable is a real breakthrough in linear heat detection
wire. With a dramatically lower resistance/ft. over competitive
products, ThermoCable allows for runs of up to 10,000' in
a single zone and the more flexible, yet rugged construction
of ThermoCable makes installation easier and less time consuming.
ThermoCable is certified by UL, ULC and FM for use with ANY
FIRE DETECTION PANEL. You don't have to purchase the Fire
Detection Panel from SAFE Fire Detection, Inc.!
|
|
Lower cost |
|
|
Up to 10,000 linear feet of ThermoCable
per zone, .05 ohms/ft resistance per twisted pair wire
(Lower than any other wire) |
|
|
Compatible with ALL Fire Alarm
Control / Releasing Panels (Maximum length determined
by resistance allowed by panel) |
|
|
Multiple alarm temperatures:
155°F, 172°F, 190°F, 220°F, 280°F,
360°F |
|
|
Distance locating available |
|
|
Can detect anywhere along the
entire length of wire |
|
|
Multiple alarm temperatures can
be mixed on the same zone |
|
|
Total zone length replacement
unnecessary after alarm |
|
|
Longer standard spool lengths
means less splicing |
|
|
Custom lengths available |
|
|
Corrosion and UV resistant |
|
|
A full assortment of mounting
and splicing hardware available |
|
|
Model
4410 Fire Alarm Control/Releasing Panel
The TC4410 Panel is a microprocessor based multi-hazard fire
alarm control /releasing panel for use on pre-action and deluge
type sprinkler systems. The TC4410 is U/L and ULC Listed (TC4410A),
FM, MEA and CSFM approved and complies with UL Standard 864
for Local Control Units for Releasing Service. It is designed
to be compatible with the requirements of NFPA-72, NFPA-13,
NFPA-15 and NFPA-16.
The TC4410 Fire Alarm Control/Releasing Panel may be used
with ThermoCable linear heat detection and providing
up to 10,000 linear feet of detection wire per zone. The TC4410
is also capable of up to 25 initiating devices such as photo/electric,
ionization, heat, UV/IR or beam detectors per zone. It may
also be used with flow and tamper switches for a complete
detection and suppression system.
|
|
Four Zone Panel, Class A or B |
|
|
Self Diagnostics circuitry for
system supervision |
|
|
32 character alpha-numeric LCD
Display |
|
|
Custom banner message text |
|
|
Custom zone description text |
|
|
Monitors up to 25 smoke detectors
per zone |
|
|
Pre-action/deluge sprinkler release,
smoke detection, flow and tamper monitoring and annunciation |
|
|
Releasing circuits protected
from false activation |
|
|
Continuous or timed discharge |
|
|
Alarm, trouble and supervisory
relays |
|
|
Available in NEMA enclosures
to suite any application |
|
|
24, 60 or 90 hour battery backup |
|
|
Complies with UL 864 |
|
|
 |